소형 수냉식 냉각기가 냉매를 충전할 때 따라야 하는 방법
In our life, we believe that everyone is very familiar with refrigeration. In the central air conditioning and industrial production process cooling industry, small water cooled chiller is more common. This unit is composed of a compressor in the fuselage, a horizontal shell and tube condenser, an evaporator, a thermal expansion valve, and some related parts. Under the cooperation of these auxiliary parts, the overall small water cooled chiller is compact in structure, convenient in operation and control, and is popular among the public in the market.
For refrigeration systems that do not have a high pressure reservoir and a low pressure vapor-liquid separator, the control of refrigerant charge is particularly important. Because the refrigeration system is a condenser and also acts as a high-pressure reservoir, the refrigerant is stored in the condenser, and the condenser is cooled. The heat dissipation area is reduced and the condensing pressure is increased, resulting in a decrease in cooling capacity.
For the control of the refrigerant charge of such small water cooled chillers, the following methods are followed during the filling process:
First, touch the temperature of the condenser casing.
The upper outlet of the condenser outlet is heated above the outlet, and the outlet below the outlet is cool. (There is a description of the high temperature exhaust of the compressor in the inside. The cooling indicates that the small water-cooled chiller is a liquid space.)
Second, look at the inspiratory pressure.
Corresponding to the temperature of the refrigerant water in the evaporator. (That is, corresponding to the evaporation temperature.)
Third, look at the compressor return pipe temperature.
The high-temperature unit return pipe should be cooled and dew, but it can be dew condensation to the compressor return valve; the low-temperature unit return pipe should be frosted, but the frost can be connected to the compressor return valve. If condensation or frost builds up on the compressor casing, liquid refrigerant will enter the crankcase, causing the compressor to run back and cause liquid problem.
관련 권장 사항
-
저온 사이클 장비 작동의 중요성 설명
1112저온 사이클 장비의 사용은 표준 작동과 분리할 수 없습니다. LNEYA 저온 사이클 장비는 해당 사용 설명서와 함께 배송되며 사용자는 사용시 미리 알 수 있습니다. 저온 ...
세부 정보 보기 -
저온 산업에서 열악한 냉동 성능과 냉매의 관계
941저온 산업용 냉장고의 냉동 시스템의 효과는 냉매와 직접적인 관련이 있습니다. 냉매가 누출되면 냉각 용량이 충분하지 않으므로 흡입 및 배기 압력이 상대적으로 ...
세부 정보 보기 -
How is the electric vehicle battery test driver grounded?
1000If the electric vehicle battery test is not isolated between the AC power source and the drive DC bus (such as a transformer), do not connect the non-isolated port of the DC bus or the ground of the non-isolated signal to the ground, which may res...
세부 정보 보기 -
액체를 100℃까지 가열하고 30℃까지 냉각하는 온도 제어 시스템
1118가열 방법으로는 증기 가열, 열유 가열 등이 있습니다. 증기 가열은 증기 공급이 가능한 공장에 적합한 보일러가 필요할 수 있으며, 열유는 고온에 적합하며 유...
세부 정보 보기