Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
관련 권장 사항
-
Dynamic and accurate temperature simulation for test benches in the automotive industry
950Quality and safety testing are the core elements of the overall development and production process of the automotive industry. With KRY-475 and 455 process cooling circulators, we provide customers with a perfect temperature control solution for p...
세부 정보 보기 -
Immersion phase change liquid cooling system
1185What is immersion phase change liquid cooling system?
세부 정보 보기 -
저온 챔버의 중요성
912저온 챔버는 일반적으로 냉장고와 테스트 부품을 분리하고 테스트 부품을 룸 타입으로 만들어 직원이 작업 할 수 있도록하는 대형 극저온 또는 극저온 테스트 장치입니다. 이러한 테스트 룸을 저온 ...
세부 정보 보기 -
Low temperature heating control chip and other detection methods
1202With the research and development of chip technology, chip detection technology is also maturing. LNEYA's low-temperature heating control chip technology is applied in chip detection. In addition to this type of detection technology, there are oth...
세부 정보 보기