Working Principle and Process of Chiller Temperature Control and Pressure Controller
Air cooled chiller temperature controller is a two – position regulator, also known as chiller temperature control relay.According to the change of adjusted temperature,the chiller temperature control makes the contact on or off, thus controlling the motor or solenoid valve of the compressor.The chiller temperature controller usually uses pressure-sensitive elements to change the temperature parameters into pressure parameters to push the contact on and off.
Operating principle of chiller temperature control: the temperature wrap and bellows are filled with volatile liquid working medium.When the temperature of the temperature wrap changes, the working medium pressure changes accordingly.If the temperature of the air-cooled chiller drops, the thrust of the bellows will be reduced.Under the action of the spring force, the lever rotates counterclockwise. The two points of lever A and B will push the button of the micro switch to make the normally closed contact disconnected, thus cutting off the circuit.On the contrary, when the temperature of the air-cooled chiller rises, the thrust of the bellows increases and the lever rotates clockwise. A and B are separated from the button of the micro switch. Under the action of the spring force of the micro switch, the contact is closed and the circuit is connected.
Air cooled chiller pressure controller: the chiller pressure controller is also a two – position regulator. It is an electrical switch controlled by a pressure signal,also known as pressure relay. The pressure controller of the air cooled chiller is divided into two types: high pressure controller and low pressure controller. It can also combine the high pressure controller and low pressure controller together, which is called high and low pressure controller.
The low-pressure controller of the air-cooled chiller is used in the steam suction pipe of the compressor. When the pressure is lower than the set value, the low-pressure controller cuts off the circuit. When the pressure is higher than the set value, the circuit is connected.The low pressure controller can also be used as the energy automatic regulation of the compressor. The left side is the high pressure controller and the right side is the low pressure controller.As the compressor overpressure protection of the high pressure controller, pressure drop, can not be automatically reset.Manual reset is required to prevent the compressor from starting up again before the failure is eliminated.
Related recommendations
-
How to repair the compressor failure in the industrial glycol temperature cycle machine
2225The industrial glycol temperature machine performs refrigeration and heating reactions under the required process conditions, and the compressor is used as its core accessory. If a fault occurs, the operator should pay attention to summarizing and...
View details -
Basic maintenance of high and low temperature refrigeration circulating pumps
2715Properly perform the sequence of opening and closing of the high and low temperature refrigeration cycle pump group to ensure normal operation after the host is started. Note that the condenser heats up well, otherwise the high temperature protect...
View details -
Features and applications of vacuum heat sink chillers
1720Vacuum heat sink chillers are a type of equipment specially designed to provide cooling in a high vacuum environment, and are typically used in scientific research, semiconductor manufacturing, aerospace, and other fields that require high...
View details -
LNEYA isolation explosion-proof cooling heating circulation system SR-35N
1514LNEYA isolation explosion-proof cooling and heating circulation system mainly uses heat transfer medium for heating and refrigerant for cooling. So what are the main accessories in the isolated cold and hot water circulation system? What effect do...
View details
LNEYA Thermo Refrigeration Co.,Ltd