Working Principle and Process of Chiller Temperature Control and Pressure Controller
Air cooled chiller temperature controller is a two – position regulator, also known as chiller temperature control relay.According to the change of adjusted temperature,the chiller temperature control makes the contact on or off, thus controlling the motor or solenoid valve of the compressor.The chiller temperature controller usually uses pressure-sensitive elements to change the temperature parameters into pressure parameters to push the contact on and off.
Operating principle of chiller temperature control: the temperature wrap and bellows are filled with volatile liquid working medium.When the temperature of the temperature wrap changes, the working medium pressure changes accordingly.If the temperature of the air-cooled chiller drops, the thrust of the bellows will be reduced.Under the action of the spring force, the lever rotates counterclockwise. The two points of lever A and B will push the button of the micro switch to make the normally closed contact disconnected, thus cutting off the circuit.On the contrary, when the temperature of the air-cooled chiller rises, the thrust of the bellows increases and the lever rotates clockwise. A and B are separated from the button of the micro switch. Under the action of the spring force of the micro switch, the contact is closed and the circuit is connected.
Air cooled chiller pressure controller: the chiller pressure controller is also a two – position regulator. It is an electrical switch controlled by a pressure signal,also known as pressure relay. The pressure controller of the air cooled chiller is divided into two types: high pressure controller and low pressure controller. It can also combine the high pressure controller and low pressure controller together, which is called high and low pressure controller.
The low-pressure controller of the air-cooled chiller is used in the steam suction pipe of the compressor. When the pressure is lower than the set value, the low-pressure controller cuts off the circuit. When the pressure is higher than the set value, the circuit is connected.The low pressure controller can also be used as the energy automatic regulation of the compressor. The left side is the high pressure controller and the right side is the low pressure controller.As the compressor overpressure protection of the high pressure controller, pressure drop, can not be automatically reset.Manual reset is required to prevent the compressor from starting up again before the failure is eliminated.
Related recommendations
-
Working Principle of Glycol Chiller
2162For the low-temperature chiller using ethylene glycol solution, we call it glycol chiller. Its outlet water temperature is generally below - 10 ℃, and the specific temperature requirements shall be subject to the needs of users. Glycol chillers a...
View details -
How to replace the scroll compressor of the impact tester model?
2748In terms of different impact tester models, the configuration is also somewhat different. Among them, special care should be taken when replacing the scroll is a compressor. If the replacement is not noticed, the impact tester cannot be used. The ...
View details -
What should I pay attention to when choosing an evaporator for an ultra-low temperature chiller?
2045The evaporator in the ultra-low temperature chiller is one of its four major components, so performance is more important. The selection of ultra-low temperature chillers needs to pay attention to the influence of liquid level on the evaporation t...
View details -
Precautions for small laboratory water chiller before and after startup
2640In the pharmaceutical and chemical industry, small laboratory water chillers are widely used refrigeration equipment, which are often used in various reaction kettles for refrigeration reactions. In order to maintain the stable operation of the eq...
View details
LNEYA Thermo Refrigeration Co.,Ltd