Causes and troubleshooting of low-temperature water chillers for photoetching machines
The operator of the low-temperature chiller for lithography machine can have a certain understanding of the related faults and solutions during the operation of the equipment, so as to better use the low-temperature chiller for lithography machine. What is the cause of the failure?

1. Refrigerant leakage:
After the refrigerant leaks in the system, the cooling capacity is insufficient, the suction and discharge pressures are low, the evaporator is not covered with frost or there is a small amount of frost at the corners, if the expansion valve hole is adjusted, the suction pressure still does not change much, and the system is balanced after shutdown The pressure is generally lower than the saturation pressure corresponding to the same environment.
Elimination method: After the refrigerant leaks, do not rush to fill the system with refrigerant, but immediately find the leakage point, and then fill the refrigerant after repair.
2. Too much refrigerant is charged after maintenance:
The amount of refrigerant charged in the refrigeration system after maintenance exceeds the capacity of the system, the refrigerant will occupy a certain volume of the condenser, reduce the heat dissipation area, and reduce the cooling effect. The suction and discharge pressures are generally higher than the normal pressure. Value, the evaporator is not frosting, and the lithography machine uses a low temperature chiller to cool down slowly.
Remedy: According to the operating procedure, the excess refrigerant must be discharged from the high shut-off valve after a few minutes of shutdown. At this time, the residual air in the system can also be discharged.
3. There is air in the refrigeration system:
Air in the refrigeration system will reduce the refrigeration efficiency. The prominent phenomenon is that the suction and discharge pressures increase (but the discharge pressure has not exceeded the rated value), and the temperature from the compressor outlet to the condenser inlet increases significantly. Air, exhaust pressure and exhaust temperature all increase.
Remedy: A few minutes after the shutdown, air can be discharged from the high-pressure shut-off valve several times in succession, and some refrigerant can be properly filled according to the actual situation.
4. The frost on the surface of the evaporator is too thick:
The cold storage evaporator used for a long time should be defrosted regularly. If it is not defrosted, the frost layer on the evaporator pipe will become thicker and thicker. When the entire pipe is wrapped into a transparent ice layer, it will seriously affect the heat transfer and cause the lithography machine The temperature of the low-temperature chiller does not fall within the required range.
Remedy: Stop the machine to defrost, and do not hit the frost layer with iron or wooden sticks to prevent damage to the evaporator pipeline.
5. There is refrigerating oil in the evaporator pipeline:
During the refrigeration cycle, some refrigerating oil remains in the evaporator pipeline. After a long period of use, when there is a large amount of residual oil in the evaporator, it will seriously affect the heat transfer effect and cause poor cooling.
Remedy: Remove the refrigerant oil in the evaporator. Remove the evaporator, blow it out, and then dry it.
After the low-temperature chiller for lithography machine has a liquid hammer failure, if the operator or user cannot solve it in time, please contact the manufacturer to solve it.
to sum up
We must clean up and maintain the equipment in time, so as to enhance the life of the equipment.
관련 권장 사항
-
Description of high and low temperature circulation tank refrigeration process
1418In the process of using high and low temperature circulating tanks, there may be some minor problems due to improper use, and there may be problems in the refrigeration process of Wuxi Guanya high and low temperature circulating tanks, and then we...
세부 정보 보기 -
산업용 글리콜 온도 사이클 기계에서 압축기 고장을 수리하는 방법
1198산업용 글리콜 온도 기계는 필요한 공정 조건에서 냉장 및 가열 반응을 수행하며 압축기는 핵심 액세서리로 사용됩니다. 고장이 발생하면 작업자는 요약에주의를 기울여야하며 ...
세부 정보 보기 -
냉각수 순환기의 모드가 주로 물 순환인 이유는 무엇인가요?
951냉각수 순환기는 물을 냉각에 사용하는 방법입니다. 주변 온도가 상승함에 따라 많은 회사에서 순환수 사용이 증가하고 있음을 발견했습니다. 순환수의 보충은 수냉을 목표로합니다 ...
세부 정보 보기 -
Factors affecting the cooling capacity of the chiller of the chemical reactor cooling system
1440There are various types of chillers, such as air-cooled chillers, water-cooled chillers, etc. But no matter what the chiller is, there are some factors that affect the cooling capacity of the chiller. A cooler is an energy-saving device that is co...
세부 정보 보기