저온 냉각기 시스템에서 발생하는 아이스 잼 현상
The phenomenon of ice jam in low temperature chiller system is mainly due to the excessive water in the refrigeration system. With the continuous circulation of refrigerants, the water in the refrigeration system gradually concentrates at the outlet of expansion valve. Because the outlet of expansion valve has the lowest temperature, the water turns into ice and the ice enlarges gradually. To a certain extent, the expansion valve will be completely blocked, resulting that the refrigerant can not be recycled, and the cold storage will not refrigerate.
The phenomenon of ice jam in low temperature 냉각기 시스템 is normal in the initial stage. There is frost in the evaporator, heat dissipation of the condenser, stable operation of the unit, clear and stable movement of refrigerant in the evaporator. With the formation of ice jam, the air flow is gradually weakened and intermittent. When the jam becomes serious, the sound of air flow completely disappears. The refrigerant cycle is interrupted. And the condenser is gradually cooled.
Because of the blockage, the exhaust pressure rises. The sound of the machine increases. There is no refrigerant flowing into the evaporator. The frost area decreases gradually. The temperature increases gradually, and the temperature of the expansion valve rises together, so the ice begins to melt. At this time, the refrigerant begins to recycle again. After a period of time, ice blockage occurs again, forming a periodic phenomenon of through-blockage.
Troubleshooting of Ice Block
The ice jam failure of low temperature chiller system is due to excessive moisture in the system, so the whole refrigeration system must be dried. There are two ways to deal with it:
1. Heat and dry the components of the refrigerant system in a drying box. Remove the compressor, condenser, evaporator, expansion valve and return pipe in the refrigerant system from the cold storage and put them into the drying box for heating and drying.
2. Remove the water content of each part of the refrigeration system by heating and secondary vacuum extraction.
관련 권장 사항
-
최적의 냉각기 솔루션을 선택하는 방법은?
1009Choosing a water chiller is like finding a "target" for an enterprise's production equipment. It must not only be "like-minded", but also "be well-matched". The one that suits you is the best. If the choice is not good, either the cooling effect ...
세부 정보 보기 -
The Difinition and Application of Heating Cooling Circulator
1028Before discussing how to choose the right brand of heating cooling circulator, we need to know the definition and application of heating and cooling circulator. Definition: thermostatic waterbath is also called the thermostatic water tank, constan...
세부 정보 보기 -
How to Control Static Electricity in Ultra-Low Temperature Test Chamber?
1045When using the ultra-low temperature test chamber, in order not to affect the quality of it, we need to better control static electricity. So how to control static electricity in Wuxi crown sub-cryogenic test chamber?Static electricity in the ultr...
세부 정보 보기 -
How to avoid operational errors in fluid heat transfer temperature control systems?
1029During the operation of the fluid heat transfer temperature control system, if the fluid heat transfer temperature control system fails, the main reason is the operation error. So how do we avoid mistakes. 1. The operation of the fluid heat trans...
세부 정보 보기