저온 냉각기 시스템에서 물 공급 문제를 해결하는 방법
Due to the improper operation of low temperature chiller system, there is the possibility of water entering into refrigerant system. Therefore, in view of the problem of water supply in low temperature chiller system, process guidance is formulated to serve as a reference for maintenance.
1. Analyse the reasons. Check the whole low temperature chiller system to confirm the cause of freezing damage and find out the leak point.
2. Blow dirt in sections.
(1) First, air compressor can be used to blow water (save nitrogen), until no water mist precipitate. Then blow with high pressure nitrogen, at the same time, heat the nitrogen (the nitrogen cylinder is prohibited from heating).
(2) Because the pipeline of low temperature chiller system is complex, water can be blown out in segments by using welding torch in some parts according to specific conditions.
(3) Heat and dry. The capillary, thermal expansion valve, compressor and other small components can be placed in the oven to bake and dry. Do replace the refrigerating oil in the compressor after the water is dried.
1. Vacuum drying
(1) Restore the pipeline and maintain the nitrogen pressure to ensure the air tightness of the system. Then connect the vacuum pump to the system for vacuum drying. (Dry filter barrel should be added to the front end of vacuum pump to avoid excessive water and gas entering the vacuum pump)
(2) In the process of vacuum drying, heat the place where water is easily stored in the pipeline, and the time can be determined according to the site.
2. Debugging and running.
(1) Make sure that the water in the system is basically removed.
(2) Connect the external drying filter barrel to the system and replace the desiccant after running for 5 minutes. At the same time, observe the operating parameters of the unit and pay attention to the sound of the compressor. If the dry filter is cold, the expansion valve frosts, and there is a pressure difference of more than 0.5 kg before and after the return air filter, stop the compressor immediately.
3. Completion of maintenance
(1) Remove the refrigerant pipe from the drying filter barrel and restore it.
(2) Check the supplementary refrigerant quantity. Turn on and check the machine running parameters to confirm normal.
관련 권장 사항
-
Temperature control range and accuracy of high and low temperature tester
1078The temperature control accuracy of heat transfer oil medium of the high and low temperature tester used for component testing is plus or minus 0.5 ℃, which solves the problem of temperature control lag in electronic components. Main advantages of...
세부 정보 보기 -
온도 충격 테스트 챔버 고장 성능 설명
1078온도 충격 테스트 챔버는 다양한 주요 산업에서 널리 사용됩니다. 사용자는 구매할 때 온도 충격 테스트 챔버를 오랫동안 사용할 수 있기를 바랍니다. 따라서 온도 충격 테스트 챔버의 각 결함을 이해할 필요가 있습니다. .
세부 정보 보기 -
100L high and low temperature thermostat installation instructions
880The 100L high and low temperature thermostat uses coolant as the transmission medium to transfer the heat generated by other instruments or equipment that need to be cooled, and dissipate the heat to the outside of the equipment through the refrig...
세부 정보 보기 -
반도체 디바이스 테스트 장비는 어떤 산업에서 사용되나요?
1197반도체 소자 테스트 장비는 반도체 산업에서 더 많이 사용됩니다. 그렇다면 해당 반도체 도체에 대해 얼마나 알고 계십니까? 이 물질의 특성은 여전히 사용자에게 권장됩니다. 일반적으로 물질은 ...
세부 정보 보기