Maintenance Method Of Ultra Low Temp Chiller Refrigeration System
The ultra low temp chiller refers to the refrigeration unit whose chilled water temperature reaches below minus 35℃. The unit adopts two-stage compression refrigeration, and the combination of the scroll compressor and the piston compressor is used to manufacture a freezing source of minus 35℃ or even minus 60 ℃, to meet the requirements of the production process, to ensure the normal and smooth production.
Firstly, the leak detection of ultra low temp chiller system.
1. The refrigerant side of the unit has undergone a strict leak detection process during the factory and commissioning process.
2. After the unit is running, check the high-pressure part with the leak detector to ensure the tightness of all connections.
3. If a leak is found, it should be disposed of immediately. In general, the connection of the nano or flange bolts can be used to eliminate the leaks, but there is also the possibility that the refrigerant be recovered and then the leaks must be treated. Such as the leakage of welded joints.
Second, the system’s pressure leak detection.
The standard pressure leak detection steps for ultra low temp chillers are as follows:
1. Fill a small amount of R-22 gas to a system pressure of 2PSIG.
2. Fill the system with nitrogen to 25~50 PSIG. Make sure the pressure reaches all parts of the system. The oil valve can be opened slightly, and the leak detector is used to check whether there is refrigerant.
3. Check each joint and weld, and try to be careful and spend as much time as possible. The leak detection equipment used must be sensitive and reliable.
4. Open the top bleed valve of the evaporator and condenser to confirm that no refrigerant has been detected. If refrigerant is found, the end cap should be removed to remove the internal leak.
5. Confirm that the system is completely sealed, and the gas is released from the system at an appropriate flow rate from the filling valve to perform a certain purging action.
Thirdly, vacuuming and drying of ultra-low temperature chiller system.
1. Connect the high efficiency vacuum pump and the mercury vacuum gauge in series with the filling valve of the system.
2. Open all valves of the system that connect the valve, the suction valve and the vacuum gauge. Confirm that all valves that pass through the atmosphere are closed.
3. Start the vacuum pump and pump the vacuum to 5mmHg.
4. If there are conditions, 50oC of hot water can be introduced into the system to accelerate the evaporation of the system’s memory and improve the dryness.
관련 권장 사항
-
How to choose the pipeline for condensing adsorption recovery vocs?
981Condensate adsorption recovery vocs device at the time of selection, its system configuration needs to be clear to be able to buy with confidence, then, the condensation adsorption recovery vocs pipeline attention points, how to choose? Condensate...
세부 정보 보기 -
Cooling method for laboratory evaporative instruments in operation
962Choosing the right cooling method for an evaporation experiment can have an unimaginable impact on overall system performance, economy, and efficiency. It is necessary to purchase cooling water circulation machine as supporting equipment. When pu...
세부 정보 보기 -
저온 실험용 증발기 기기가 냉동 시스템에 미치는 영향
1216다른 모델에 따라 저온 실험 특수 기기의 증발기 선택도 상자 형 저온 실험 특수 기기, 물 탱크 코일 증발기를 사용하는 것과 같이 저온 실험 특수 기기의 증발기 선택이 다릅니다.
세부 정보 보기 -
저온 냉각기의 응축기 유지보수
973최근 몇 년 동안 중국의 산업 생산 수준이 향상됨에 따라 많은 전문 산업 기계 및 장비가 다양한 산업 생산에 더 큰 도움을 제공합니다. 매우 실용적인 산업용 냉동 장비로서 ...
세부 정보 보기