What to do When the High Pressure Alarm of the Chiller?
People must pay attention to the maintenance of large-scale temperature control equipment such as industrial water chiller. Sometimes it is normal to encounter high-pressure alarm. We must first find out the causes of high-pressure of the industrial water chiller, and then we can solve the problem according to the remedy.

The causes of high pressure fault of industrial water chiller are as follows:
(1) The cooling water flow is insufficient to reach the rated water flow. The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller (compared with the pressure difference at the beginning of system operation), and the temperature difference becomes larger. The reason for insufficient water flow is the lack of water or air in the system. The solution is to install an exhaust valve at the height of the pipeline for exhaust. If the pipeline filter is blocked and the water permeability is limited, appropriate filter shall be selected and the filter screen shall be cleaned regularly; The water pump is small and does not match the system.
(2) The cooling water temperature is too high and the condensation effect is not good. The rated working condition of cooling water required by the chiller is 30 ~ 35 ℃, high water temperature and poor heat dissipation effect will inevitably lead to high condensation pressure, which often occurs in high temperature season. The reason for high water temperature may be: cooling tower failure, such as the fan is not turned on or even reversed, and the water distributor does not turn, which shows that the cooling water temperature is very high and rises rapidly. The external temperature is high, the waterway is short and the amount of recyclable water is small. In this case, the cooling water temperature is generally maintained at a high level, which can be solved by increasing the water storage tank.
If you have seen the above two solutions and have other problems, you can contact us sales@lneya.com 。 We lneya have professional technical engineers who can help you solve your questions.
관련 권장 사항
-
The reason why the semiconductor small thermostat is blocked by refrigeration
1271The small semiconductor small-scale thermostat ice jam is mainly caused by the excessive moisture contained in the refrigeration system. With the continuous circulation of the refrigerant, the moisture in the refrigeration system gradually collect...
세부 정보 보기 -
Explosion-proof ultra-low temperature refrigerator internal leakage instructions
13181. Sound leak detection method: First, the refrigeration pipeline of the explosion-proof ultra-low temperature refrigerator is filled with nitrogen. Then use a stethoscope to check the interior. When you hear a leak in a certain area, mark it. Car...
세부 정보 보기 -
바이오 제약 실험실 오일 쿨러의 안정적인 성능을 유지하는 방법은 무엇입니까?
9341. A suitable working environment to prevent various failures of the oil cooler in the biopharmaceutical laboratory needs to provide a better operating environment for the equipment. Keep the environment clean and tidy, reduce the impact of vario...
세부 정보 보기 -
2018 CIPM China | You have an invitation to the exhibition from LNEYA
1270The 56th (Fall 2018) National Pharmaceutical Machinery and China International Pharmaceutical Machinery Expo will be held from November 5th to November 7th, 2018 at Wuhan International Expo Center. As one of the professional communication platfor...
세부 정보 보기