Explanation of Abnormal Condenser Temperature of Glycol Chiller
In the glycol chiller, the condenser temperature is the saturation temperature when the refrigerant in the condenser condenses under the steam pressure. Once the condenser temperature in the glycol chiller is abnormal, we should analyze the specific causes and find out the solutions.

The condenser temperature of glycol chiller is low
The low temperature of the condenser of the glycol chiller may be due to the large selection of the expansion valve, the failure of the expansion valve or the excessive opening of the expansion valve, which can not achieve the throttling effect. It may also be that the refrigerant charge of the refrigeration system of the glycol chiller is relatively small, which can not reach the specified amount, or the refrigeration system is lack of corresponding refrigerant.
The condenser temperature of glycol chiller is too high
The main reasons for the high temperature of the condenser of the glycol chiller are: the cooling water (or air) flow of the glycol chiller is small, the temperature is too high, or there is air in the refrigeration system of the glycol chiller, which increases the pressure of the condenser of the glycol chiller. Excessive refrigerant charge and insufficient effective condensation area can also lead to high condenser temperature of glycol chiller. If the condenser is out of repair for a long time and the dirt on the heat transfer surface is serious, it can also lead to the increase of condensation pressure, and the existence of scale also has a great impact on the condensation pressure.
Solution to high or low condenser temperature of glycol chiller
The higher or lower condenser temperature of glycol chiller will lead to abnormal compressor exhaust temperature and reduced output coefficient, so as to reduce the refrigeration capacity and increase the power consumption of the compressor. If the exhaust temperature of glycol chiller is too high, the consumption of compressor lubricating oil will be increased and the oil will become thin.
When the exhaust temperature is close to the flash point of compressor oil, some lubricating oil will be carbonized and accumulated at the suction and exhaust valve ports, affecting the tightness of the valve. At this time, it is necessary to reduce the temperature of the cooling medium to reduce the condensation temperature and the condensation pressure, but this is limited by environmental conditions and is difficult to choose artificially.
Increasing the flow of cooling medium can reduce the condensation temperature a little, but it can not unilaterally increase the flow of cooling water or air, because it will increase the power of cooling water pump, fan and motor. It should be comprehensively considered that high exhaust pressure will increase the compression work and reduce the gas transmission coefficient, so as to reduce the refrigeration efficiency. The condenser temperature of glycol chiller is closely related to the smooth operation of glycol chiller, so users should solve it in time if they find that the condenser temperature is abnormal.
관련 권장 사항
-
How to judge the operating status of the chemical and pharmaceutical constant temperature control sy
977Nowadays, many pharmaceutical and chemical industries use LNEYA's constant temperature control system. How to judge its operation status during operation? There should be no noise in the cylinder of the chemical and pharmaceutical thermostatic con...
세부 정보 보기 -
중추절 감사 만찬이 성황리에 종료되었습니다.
1465The autumn wind is refreshing, and the Mid-Autumn Moon is rounder. At the juncture of time, the annual Mid-Autumn Festival is about to usher in. In this beautiful festival, Wuxi Guanya is full of love and the Mid-Autumn Festival Appreciation Dinn...
세부 정보 보기 -
Energy-efficient high and low temperature circulation box description
1181With the efficient development of the pharmaceutical and chemical industry, environmental pollution is also the subject of more attention. To this end, LNEYA actively responds to environmental protection, produces energy-efficient and high-tempera...
세부 정보 보기 -
산업용 재순환 냉각기의 구조적 특성
898화학 반응에는 반응 온도에 대한 엄격한 요구 사항이 있습니다. 화학 반응을 원활하게 수행하려면 온도를 적절한 온도로 높여야 합니다. 반응 후, 다시 온도는 ...
세부 정보 보기