What are the common debugging problems in low temperature refrigeration baths?
When the low-temperature cooling bath is in debugging, if the local cooling effect is not good, the system may be blocked by foreign matter or the system design is unreasonable and cannot be adjusted normally. At this time, LNEYA removes foreign matter and thoroughly cleans it to adjust the slope of the pipeline.
When debugging, it is found that the vibration and noise of the pump are large when it is running. It may be that the axial and radial deviation of the coupling is large. It may be that the pump flange is too large and the anchor bolts are unevenly stressed. It is the natural vibration frequency of the pump and the pipeline that cause resonance. At this time, the axial and radial deviation of the coupling are adjusted quickly. Adjust the natural vibration frequency between the pump and the pipe, install the relevant soft joint parts, replace the flange and make the anchor bolts evenly.
During commissioning, it was found that the cooling capacity could not reach the required fixed value. It may be that the cooling tower water temperature did not reach the specified cooling parameter, or the pump output was insufficient, or the condenser isolation gasket was misplaced and could not be cooled, or the pipeline in the condenser was blocked. Repair the cooling tower to meet the water temperature and water requirements, remove foreign matter in the pipeline, and check if the condenser isolation gasket is misaligned.
If the exhaust pressure is too high, it is necessary to pay attention to whether the cooling water is insufficient, whether the condensation in the condenser heat transfer tube is serious, whether the cooling water temperature is too high, whether there is too much air in the system, check the cause, repair the cooling tower, and heat transfer of the condenser. The tube is cleaned to remove air from the system.
If severe frost formation is found, check if the return air filter is clogged, if the exhaust air volume is loose after the fan belt is loose, and if the return air valve is too small, it is recommended to clean the return air filter and adjust the fan belt. Adjust the size of the return air valve.
Common faults encountered in the commissioning of these low-temperature refrigeration baths, we try to check them before debugging, try to avoid these faults.
Related recommendations
-
The Product Categories of Low Temp Chillers
2278The low temp chiller is a kind of professional refrigeration design with large demand in domestic industrial market. Many enterprises need to use low temp chiller products to create low temperature environment in industrial production. Different i...
View details -
How to maintain the high and low temperature cooling constant temperature system?
1933The high and low temperature cooling constant temperature system performs refrigeration and heating operation in the pharmaceutical and chemical industry. It follows the rules of operation and meticulous requirements to continuously improve its qu...
View details -
Chiller for heat deflection temperature instrument
2109Temperature range: The temperature of the cooling water is usually required to be between 6 ℃ and 18 ℃.Temperature difference requirement: The temperature difference of the cooling water should be controlled wit...
View details -
Integrated control system high and low temperature cycle device ZLF series use items
2117With the development of society, the chemical industry has been further developed, and the temperature system control of the reactor has been strengthened, so as to ensure that the monitoring environment is in a good state, to ensure that the temp...
View details
LNEYA Thermo Refrigeration Co.,Ltd