Treatment of insufficient exhaust gas in high and low temperature impact test chamber compressor
The efficiency of the high and low temperature impact test chamber during use is very important. If there is a shortage of high compressor exhaust, we need our LNEYA technicians to solve it in time. So, how to solve it better?
The high and low temperature impact test chamber filter is fouled and the exhaust volume is reduced. Need to clean the filter in time to solve the problem. The suction pipe is too long, and the pipe diameter is too small, so that the increase of the suction resistance affects the gas volume; it is necessary to increase the pipe diameter of the suction pipe in time and shorten the length of the suction pipe.
Because the air compressor is designed according to a certain altitude, intake temperature and humidity, how to use it at high altitude, the suction pressure will decrease, and the exhaust volume will be insufficient. It is necessary to replace the appropriate high and low temperature impact test chamber compressor in time.
The cylinders, pistons and piston rings are severely worn and out of tolerance, which increases the relevant clearance and increases the leakage, which affects the displacement. If it is necessary to be in time for normal wear and tear, it is necessary to replace consumable parts in time, such as piston rings. If the installation is inaccurate and the gap is left in a timely manner, it should be corrected according to the drawings.
The packing box of the high and low temperature impact test chamber is not strict, and the negative air volume is reduced. The reason is firstly because of the divergence requirements in the manufacture of the stuffing box itself; secondly, because during the installation, the center of the piston rod and the stuffing box is not well, causing air leakage due to wear and strain; generally, the lubricating oil is filled in the stuffing box. It can function as lubrication, sealing and cooling.
Metal fragments or other debris are dropped between the valve seat and the valve plate, resulting in a tight seal and a leak. This not only affects the amount of exhaust, but also affects the pressure and temperature changes between the two stages. This problem may arise because of the manufacturing quality problems, such as valve warpage, and the second, because the valve seat and the valve plate wear. Severe and leaking.
The valve spring force does not match the gas force. If the elastic force is too strong, the valve plate will be opened slowly. If the elastic force is too weak, the valve plate will not be closed. This will not only affect the air volume, but also affect the increase of power and the life of the valve disc and spring. At the same time, it also affects changes in gas pressure and temperature.
The pressing force of the compression valve is improper. If the pressing force is small, it will leak air. Of course, it will not be too tight, which will deform and damage the valve cover. The valve has a fault, the bonnet has a fever, and the pressure is not normal.
These faults of the high and low temperature impact test chamber need to be solved in time after some faults are found. At the same time, it is necessary to pay more attention to maintenance and reduce the failure rate.
Related recommendations
-
Performance description of recirculating chiller for bioreactor
2148The recirculating chiller is suitable forthe high and low temperature reaction of various stainless steel, enamel,titanium alloy reactors, emulsifiers, injection molding machines, mixingvessels and various bioreactors. Other bioreactors in diff...
View details -
Several Big Considerations for Enterprises When Using Heating Coolers
2225In addition to the above-mentioned enterprises, which should arrange for someone to be responsible for the start and stop of refrigerators, switches, and repairs and maintenance. The precautions for the use of refrigerators in enterprises are as f...
View details -
Working state of temperature control circulating device for purification of small-scale distillation
1975Distillation reflux concentration and purification temperature-control circulating device is widely used in many fields. It is very important to select appropriate equipment, which can greatly improve product quality and reduce production costs t...
View details -
Function of Water Pump of Industrial Water Chiller
2069The water pump is one of the important auxiliary components of the refrigeration system of the industrial water chiller. Many industries will use the industrial water chiller, but many people don't know much about the equipment. This time, lneya r...
View details