Troubleshooting of Common Faults of Industrial Water Chiller
As we all know, with the rapid development of modern industrial technology, in order to improve production efficiency, improve product quality and reduce consumption costs, the demand for temperature control equipment in the process is higher and higher, but there are more and more product quality problems about some industrial water chillers, So we simply analyze some common problems about industrial water chillers.
Abnormal temperature at the inlet and outlet of cooling water: the water temperature at the inlet of condenser is too high (higher than 32 ℃), first check whether the fan of cooling tower can be reversed (there are such examples in practical engineering). Then, after technical demonstration and on the premise of feasibility, adjust the blade angle of the fan to improve the air volume of the fan.
Another phenomenon often occurs in the system with multiple cooling towers in parallel. When the local load is running, the temperature difference between the inlet and outlet of the condenser is too small. It is necessary to check whether each cooling tower has been equipped with an electric valve, or whether the set electric valve fails to form a cooling water bypass, which can not be cooled completely.
The differential pressure at the inlet and outlet of cooling water is abnormal. According to the relevant refrigeration theory, the heat release of the condenser will directly affect the refrigeration capacity. Therefore, the user should first check the cooling water system based on the pressure loss value on the main engine. If the pressure difference obtained from the value of the pressure gauge at the inlet and outlet greatly exceeds the normal value, it indicates that there are sundries at the inlet of the condenser.
Related recommendations
-
What are the applications of steam circulators in chemical industry?
2040The steam circulator in the chemical industry is a temperature control equipment in the pharmaceutical and chemical industry. When users operate, they need to understand the performance and maintenance knowledge in order to operate the equipment e...
View details -
How to solve the shortage of cooling in the semiconductor cooling cycle system
2252The semiconductor cooling cycle system is a device for cooling the semiconductor heat-generating part in the refrigeration equipment. If the cooling capacity of the LNEYA semiconductor cooling circulation system is insufficient during operation, i...
View details -
What do the LNEYA chiller fault codes mean? What is the solution?
3170Q: What is the fault code of the chiller? Answer: E1 means extremely high indoor temperature alarm, E2 means extremely high temperature alarm, E3 means extremely low temperature alarm, E4 means indoor temperature controller failure, E5 means water...
View details -
Organic waste gas recovery unit refrigeration oil requirements description
3044The organic waste gas recovery device is slightly different for different gases. The LNEYA organic waste gas recovery device and the vocs gas condensation recovery device are operated by the principles of condensation and adsorption. The refrigera...
View details
LNEYA Thermo Refrigeration Co.,Ltd