Troubleshooting of Common Faults of Industrial Water Chiller
As we all know, with the rapid development of modern industrial technology, in order to improve production efficiency, improve product quality and reduce consumption costs, the demand for temperature control equipment in the process is higher and higher, but there are more and more product quality problems about some industrial water chillers, So we simply analyze some common problems about industrial water chillers.
Abnormal temperature at the inlet and outlet of cooling water: the water temperature at the inlet of condenser is too high (higher than 32 ℃), first check whether the fan of cooling tower can be reversed (there are such examples in practical engineering). Then, after technical demonstration and on the premise of feasibility, adjust the blade angle of the fan to improve the air volume of the fan.
Another phenomenon often occurs in the system with multiple cooling towers in parallel. When the local load is running, the temperature difference between the inlet and outlet of the condenser is too small. It is necessary to check whether each cooling tower has been equipped with an electric valve, or whether the set electric valve fails to form a cooling water bypass, which can not be cooled completely.
The differential pressure at the inlet and outlet of cooling water is abnormal. According to the relevant refrigeration theory, the heat release of the condenser will directly affect the refrigeration capacity. Therefore, the user should first check the cooling water system based on the pressure loss value on the main engine. If the pressure difference obtained from the value of the pressure gauge at the inlet and outlet greatly exceeds the normal value, it indicates that there are sundries at the inlet of the condenser.
Related recommendations
-
Chiller for heat deflection temperature instrument
2128Temperature range: The temperature of the cooling water is usually required to be between 6 ℃ and 18 ℃.Temperature difference requirement: The temperature difference of the cooling water should be controlled wit...
View details -
The Application of Cold Plate Freezer
1857The refrigeration system of cold plate freezer adopts secondary super-cooler technology with the rapid refrigeration and low limiting temperature. It uses imported brand name semi-hermetic piston compressors, semi-hermetic piston compound compress...
View details -
Instructions for using the hydrogenation reactor cooling and heating integrated system
2414There are many accessories in the hydrogenation reactor cooling and heating integrated system, from the compressor to the electrical components. LNEYA reminds you that if you find more evaporator freezing oil, it is recommended to deal with it in ...
View details -
How to solve the failure of the automatic temperature control system of the reactor?
2247The performance of the automatic temperature control system of the reactor is very important. Once you encounter a failure that cannot be started, you must solve it as soon as possible, otherwise the uncontrollable temperature will affect the reac...
View details
LNEYA Thermo Refrigeration Co.,Ltd