Explanation of Abnormal Condenser Temperature of Glycol Chiller
In the glycol chiller, the condenser temperature is the saturation temperature when the refrigerant in the condenser condenses under the steam pressure. Once the condenser temperature in the glycol chiller is abnormal, we should analyze the specific causes and find out the solutions.

The condenser temperature of glycol chiller is low
The low temperature of the condenser of the glycol chiller may be due to the large selection of the expansion valve, the failure of the expansion valve or the excessive opening of the expansion valve, which can not achieve the throttling effect. It may also be that the refrigerant charge of the refrigeration system of the glycol chiller is relatively small, which can not reach the specified amount, or the refrigeration system is lack of corresponding refrigerant.
The condenser temperature of glycol chiller is too high
The main reasons for the high temperature of the condenser of the glycol chiller are: the cooling water (or air) flow of the glycol chiller is small, the temperature is too high, or there is air in the refrigeration system of the glycol chiller, which increases the pressure of the condenser of the glycol chiller. Excessive refrigerant charge and insufficient effective condensation area can also lead to high condenser temperature of glycol chiller. If the condenser is out of repair for a long time and the dirt on the heat transfer surface is serious, it can also lead to the increase of condensation pressure, and the existence of scale also has a great impact on the condensation pressure.
Solution to high or low condenser temperature of glycol chiller
The higher or lower condenser temperature of glycol chiller will lead to abnormal compressor exhaust temperature and reduced output coefficient, so as to reduce the refrigeration capacity and increase the power consumption of the compressor. If the exhaust temperature of glycol chiller is too high, the consumption of compressor lubricating oil will be increased and the oil will become thin.
When the exhaust temperature is close to the flash point of compressor oil, some lubricating oil will be carbonized and accumulated at the suction and exhaust valve ports, affecting the tightness of the valve. At this time, it is necessary to reduce the temperature of the cooling medium to reduce the condensation temperature and the condensation pressure, but this is limited by environmental conditions and is difficult to choose artificially.
Increasing the flow of cooling medium can reduce the condensation temperature a little, but it can not unilaterally increase the flow of cooling water or air, because it will increase the power of cooling water pump, fan and motor. It should be comprehensively considered that high exhaust pressure will increase the compression work and reduce the gas transmission coefficient, so as to reduce the refrigeration efficiency. The condenser temperature of glycol chiller is closely related to the smooth operation of glycol chiller, so users should solve it in time if they find that the condenser temperature is abnormal.
관련 권장 사항
-
The Analysis Of Ultra Low Freezer’S Price
1242What are the characteristics and functions of ultra low freezer:1. Ultra low freezer can prevent the precision of machine equipment from being influenced by the change of oil temperature in the process of operation. 2. Ultra low freezer can preven...
세부 정보 보기 -
Dual-channel chillers for semiconductor manufacturing industry
1019Dual-channel chillers are used in a variety of processes in the semiconductor manufacturing industry. The main purpose is to provide precise temperature control to ensure that the equipment in the semiconductor manufacturing process operat...
세부 정보 보기 -
Precautions for cooling and heating during operation of various reactors
960In many laboratories, various reaction vessels of chemical companies are indispensable reaction vessels, and its operating temperature: -80°C-250°C. The laboratory reactor works at normal temperature, and cooling water must be passed normally to a...
세부 정보 보기 -
40GW 극저온 냉각기의 유형 선택 및 분류에 대한 설명
1190If different enterprises and different industries have different requirements for Wuxi Guanya 40GW cryogenic chillers, its model selection is also different. So it is better to have a clear understanding of the needs of the selection of 40GW cryog...
세부 정보 보기