Ultra-low temperature freezing manufacturer analyzes the cause of blockage in refrigeration system
With the continuous development of technology, ultra-low temperature refrigeration technology is also constantly developing, and manufacturers are also increasing. Of course, the technology of different manufacturers is different. Once the refrigeration system is blocked, it needs to be solved in time.
If the refrigeration system of the ultra-low temperature freezer is clogged, it is necessary to understand that the formation of the clogging fault in the refrigeration system is caused by excessive impurities in the refrigeration system. The impurities in the refrigeration system of the ultra-low temperature freezer are derived from dust and metal chips in the manufacturing process. When the inner wall surface of the oxide layer falls off; the inner and outer surfaces of the parts are not cleaned during the processing; the pipeline is not tightly sealed and dust enters the tube, and the refrigerator oil and the refrigerant contain impurities.
The clogging of the refrigeration system has a certain influence on the ultra-low temperature freezer, which causes the refrigerant to be unable to circulate, the compressor is continuously operated, the evaporator is not cold, the condenser is not hot, the compressor casing is not hot, and there is no airflow sound in the evaporator. The evaporator has a cold or cold feel, but it does not frost. When you touch the outer surface of the filter and capillary, it feels cool, has frost, and even forms a layer of hoarfrost.
If the cryogenic refrigerator refrigeration system is clogged, it is recommended to use a drying oven to heat and dry the components. The compressor, condenser, evaporator, capillary, and return air hose in the refrigerant system are removed from the refrigerator and placed in a drying oven. The inside is heated and dried, the temperature in the box is about 120 ° C, and the drying time is 4 hours. After being naturally cooled, the air is blown and dried one by one with nitrogen. Replace the new desiccant filter and then assemble and weld, pressurize and leak, vacuum, fill the refrigerant, test run and seal.
The ultra-low temperature freezer also uses a heating vacuum and a secondary vacuum to remove moisture from various components of the refrigeration system. The high-pressure nitrogen gas was used to blow out the dirt in the capillary tube, and the process tube was cut and the liquid was drained. After the capillary tube was unblocked, 100 ml of carbon tetrachloride was added for aeration cleaning. The cleaning of the condenser can be carried out with carbon tetrachloride on the pipe cleaning device. Then replace the dry filter, and then add nitrogen to leak, vacuum, and fill the refrigerant.
Wuxi Guanya LNEYA ultra-low temperature refrigeration technology manufacturers refrigeration technology using single-machine self-cascade refrigeration technology, its configuration also uses brand accessories configuration, so that the operation of ultra-low temperature freezer keeps running smoothly.
Related recommendations
-
Reactor Thermal Control Unit and Solutions for Chemicals
2846Temperature control is a process in which the temperature of a substance or a change in temperature is measured or otherwise detected, and the transfer of thermal energy into or out of the space or substance is adjusted to achieve the desired temp...
View details -
How to install -60°C cryogenic chiller manufacturers equipment
2449-60℃ cryogenic chillermanufacturers are used in the refrigeration and chemical industry, so whatissues should be paid attention to during installation? LNEYA professionalmanufacturers tell you that you should install according to the instructio...
View details -
Cryogenic storage tank (explosion proof) chemical cryogenic storage
2444Product Overview:Microcomputer control, multiple security protection, and more reliable operation; Single-compressor automatic cascade supercooling refrigeration technology; compressors use Secop and France Taikang brandContactors and circuit br...
View details -
Usage Details of High and Low Temperature Environmental Chambers
2249The enterprise users must have a certain understanding of the functions of the high and low-temperature environmental chamber after using them for a long time, but something detail of the high and low-temperature environmental chamber may still no...
View details
LNEYA Thermo Refrigeration Co.,Ltd