Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
관련 권장 사항
-
Popularization of knowledge of Semiconductor Back-End Test high and low temperature control system
1115The Semiconductor Back-End Test high and low temperature control system is a necessary testing equipment for the metal, component, electronic and other material industries. It is used to test the degree of endurance of material structures or compo...
세부 정보 보기 -
Refrigeration effect of water-cooled chiller at -15℃
903The main configurations of water-cooledchillers are: compressors, electrical components, water pumps, evaporators,condensers, high/low pressure controllers, high/low pressure gauges, LCDthermostats, expansion valves, antifreeze switches, hand v...
세부 정보 보기 -
글리콜 냉각기 설치 시 주의사항은 무엇인가요?
1062In the summer, the use of glycol chillersis relatively frequent. Therefore, when installing glycol chillers, they needto be installed on a smooth and tidy floor. Why choose a smooth ground wheninstalling? Users who have known the glycol chiller...
세부 정보 보기 -
Performance Test of Household Refrigerator Designed by Environmental Chamber Sales
1351Many performance items of household refrigerators are tested under a specific environmental condition. The thermal condition of the air distribution in the environmental chamber is more severe than that in the general artificial constant temperatu...
세부 정보 보기