HIGHLY TEMPERATURE CONTROL SYSTEMS
SUNDI Z 주파수 변환 시리즈
-80℃~250℃- 냉각 용량0.4kW~60kW
- 난방 전력3.5kW~60kW
- 냉매R404A/R507C/R508B
- 무게115KG~300KG
Air-cooling & Water-cooling

왓츠앱

디테일의 이점, 우수성을 위한 노력

구성 세부 정보
모델 | SUNDIZ4-3 | SUNDIZ4-5 | SUNDIZ4-10 | SUNDIZ4-15W | SUNDIZ4-20W | SUNDIZ4-30W | |
SUNDIZ4-3W | SUNDIZ4-5W | SUNDIZ4-10W | |||||
온도 범위 | -45℃~250℃ | ||||||
난방 전력 | 5.5kW | 7.5kW | 15kW | 25kW | 38kW | 60kW | |
냉각 용량 kW | 250℃ | 5.5kW | 7.5kW | 15kW | 25kW | 38kW | 60kW |
20℃ | 5.5kW | 7.5kW | 15kW | 25kW | 38kW | 60kW | |
-15℃ | 2.3kW | 3.6kW | 7.5 kW | 11kW | 15kW | 33kW | |
-35℃ | 0.9kW | 1.5kW | 3.3 kW | 5kW | 6.5kW | 10kW | |
중간 온도 제어 정확도 | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ | |
공정 온도 제어 정확도 | ±0.3℃ | ±0.3℃ | ±0.3℃ | ±0.3℃ | ±0.3℃ | ±0.3℃ | |
펌프 유량 최대 압력 | 50L/min | 50L/min | 100L/min | 150L/min | 250L/min | 400L/min | |
2bar | 2bar | 2bar | 2.5bar | 2.5bar | 2.5bar | ||
냉매 | R-404A / R507C 可选配R448 | ||||||
인터페이스 크기 | G3/4 | G3/4 | G1 | DN32 PN10 | DN40 PN10 | DN50 PN10 |
모델 | SUNDIZ8-3W | SUNDIZ8-4W | SUNDIZ8-6W | SUNDIZ8-10W | SUNDIZ8-15W | |
온도 범위 | -80℃~+250℃ | |||||
난방 전력 kW | 3.5 | 5.5 | 7.5 | 10 | 15 | |
Cooling capacity kW @ | 250℃ | 3.5 | 5.5 | 7.5 | 15 | 20 |
20℃ | 3.5 | 5.5 | 7.5 | 15 | 20 | |
-60℃ | 1.3 | 1.8 | 3 | 5.5 | 8 | |
-75℃ | 0.4 | 0.6 | 1 | 1.8 | 2.7 | |
Medium temperature control accuracy | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ | |
Process temperature control accuracy | ±0.3℃ | ±0.3℃ | ±0.3℃ | ±0.3℃ | ±0.3℃ | |
Pump flow & pressure 최대 |
35L/min | 50L/min | 100L/min | 150L/min | 250L/min | |
2bar | 2bar | 2bar | 2.5bar | 2.5bar | ||
냉매 | Primary R-404A + Secondary R508B | |||||
인터페이스 크기 | G3/4 | G3/4 | G1 | DN32 PN10 | DN40 PN10 | |
전원 공급 장치 | 380V 50HZ / 460V 60HZ |
시스템 압력 표시 | 압력 센서가 냉장 시스템과 순환 시스템의 압력을 감지하여 터치 스크린에 표시합니다. | |||||
컨트롤러 | Siemens S7-1200PLC, fuzzy PID control algorithm, with process dynamic control algorithm | |||||
온도 제어 | 열전달 매체 출구 온도 제어 모드 | |||||
External temperature sensor: (PT100 or 4-20mA or communication setting) Control mode (process dynamic control algorithm) |
||||||
프로그래밍 가능 | 25 programs can be knitted, each program can be edited with 85 steps | |||||
통신 프로토콜 | Ethernet interface TCP/IP protocol, RS485 interface MODBUS protocol | |||||
Internal temperature feedback | Equipment heat transfer medium outlet temperature, medium inlet temperature, refrigeration system condensation temperature, ambient temperature, compressor suction temperature, cooling water temperature (for water cooling equipment) | |||||
External temperature feedback | PT100 or 4~20mA or communication setting | |||||
Cascade control | 출구 온도와 외부 온도 센서 사이의 온도 차이를 설정하고 제어할 수 있습니다; | |||||
Temperature difference control function | The temperature difference between the equipment inlet temperature and the outlet temperature can be set and controlled (to protect system safety) | |||||
폐쇄형 순환 시스템 | The entire system is a fully enclosed system. There will be no oil mist at high temperatures and no absorption of moisture in the air at low temperatures. The system will not increase pressure due to high temperatures during operation, and will automatically replenish heat transfer media at low temperatures. | |||||
난방 | Refers to the maximum heating output power of the system (depending on the model) | |||||
히터에는 3중 보호 기능과 독립 온도 제한기가 있어 난방 시스템의 안전을 보장합니다. | ||||||
Use a voltage regulator to control the heating output and reduce the heater output current in process temperature control | ||||||
냉각 | It refers to the ability to take away heat at different temperatures (under ideal conditions). The actual working conditions need to consider the heat dissipation of the environment. Please enlarge it appropriately and take insulation measures. | |||||
External circulation pump flow & pressure | 브랜드 자기 구동 가변 주파수 펌프 | |||||
compressor | Emerson, Mitsubishi and other inverter compressors | |||||
주파수 변환기 | ABB and other well-known brands | |||||
증발기 | 316L plate heat exchanger | |||||
냉장 액세서리 | Danfoss/Emerson accessories (drying filter, oil separator, high and low pressure protector, expansion valve) | |||||
조작 패널 | Wuxi Guanya customized 7-inch color touch screen, temperature curve display, EXCEL data export | |||||
안전 보호 | It has self-diagnosis function; phase sequence failure protector, refrigerator overload protection, overload relay, thermal protection device and other safety protection functions. | |||||
냉매 | R-404A/R507C 옵션 R448 | |||||
수냉식 콘덴서 | Standard plate heat exchanger | |||||
Casing material | Cold rolled steel plate spraying (standard color RaL7035) |

초고온 냉각 기술은 300℃의 고온에서 직접 냉각이 가능하며[팽창 챔버의 열전달 매체만 공기 중의 산소와 접촉하기 때문에(팽창 탱크의 온도는 상온과 60℃ 사이) 열전달 매체가 산화되고 공기 중의 수분을 흡수할 위험을 줄일 수 있습니다. 고온에서는 열전도 매체가 증발하지 않으며 -80℃ ~ 190℃, -70℃ ~ 220℃, -88℃ ~ 170℃, -55℃ ~ 250℃, -30℃ ~ 300℃의 연속 온도 제어를 가압 없이도 실현할 수 있습니다.
FLUID CIRCULATION CLOSED TEMPERATURE CONTROL

The fully enclosed pipeline design and high-efficiency plate heat exchanger reduce the demand for thermal fluid while improving the system’s heat utilization rate and achieving rapid temperature rise and fall. The thermal medium is in a closed system with an expansion container. The thermal medium in the expansion container does not participate in the circulation. Regardless of high or low temperatures, the expansion tank temperature is kept at room temperature to 60°C, effectively reducing the risk of the thermal medium absorbing moisture and volatilizing during operation.
WIDE RANGE OF APPLICATION INDUSTRY SERVICES

응용 분야: 다양한 반응기(마이크로채널, 유리, 재킷형 반응기 등), 증류 또는 추출 시스템, 실험실, 대학, 연구소, 항공우주, 자동차 산업, 반도체 및 전기 테스트, 화학, 제약, 석유화학, 생화학, 의료, 병원, R&D 작업장, 항공우주, 생물학 및 기타 산업.
APPEARANCE DETAILS OUALITY CONTROL

다음 제품에도 관심이 있을 수 있습니다.
SUNDI -10℃~150℃
완전 밀폐형 시스템, 단일 매체로 냉장 및 가열 완료 -120 ~ 350 ℃ ± 0.5 ℃ AC 380V 50HZ 8kW 최대 초고온 냉각 기술은 높은 온도에서 직접 냉각 할 수 있습니다 ...
SUNDI -80℃~250℃
작동 온도 -120°C ~ +350°C ● 이전에는 달성할 수 없었던 성능 ● 지능형 온도 제어 ● 최고의 공정 안정성 및 재현성 ● 판형 열교환기, 파이프라인 가열, 가장 빠른 열...
SUNDI-320/320W
완전 밀폐형 시스템, 단일 매체로 냉장 및 가열 완료 -120~350℃ ±0.5℃ 초고온 냉각 기술은 300℃ 고온에서 직접 냉각할 수 있습니다. Bec...
SUNDI -25℃~200℃
완전 밀폐형 시스템, 단일 매체로 냉장 및 가열 완료 -120~350℃ ±0.5℃ ● 작동 온도 -120°C ~ +350°C ● 이전에는 달성할 수 없었던 성능 ● 지능형 온도 제어...
SUNDI -45℃~250℃
작동 온도 -120°C ~ +350°C● 이전에는 달성할 수 없었던 성능● 지능형 온도 제어● 최대 공정 안정성 및 재현성● 판형 열교환 기, 파이프 라인 가열, 가장 빠른 가열을 채택합니다 ...
SUNDI -60℃~250℃
초고온 냉각 기술은 300℃의 고온에서 직접 냉각할 수 있습니다[팽창 챔버의 열전달 매체만 산소와 접촉하기 때문에...
SUNDI -80℃~250℃
작동 온도 -120°C ~ +350°C ● 이전에는 달성할 수 없었던 성능 ● 지능형 온도 제어 ● 최고의 공정 안정성 및 재현성 ● 판형 열교환기, 파이프라인 가열, 가장 빠른 열...
SUNDI -90℃~250℃
작동 온도 -120°C ~ +350°C● 이전에는 달성할 수 없었던 성능● 지능형 온도 제어● 최대 공정 안정성 및 재현성● 판형 열교환 기, 파이프 라인 가열, 가장 빠른 가열을 채택합니다 ...
SUNDI -100℃~100℃
작동 온도 -120°C ~ +350°C ● 이전에는 달성할 수 없었던 성능 ● 지능형 온도 제어 ● 최고의 공정 안정성 및 재현성 ● 판형 열교환기, 파이프라인 가열, 가장 빠른 열...
로딩 중...
이미 마지막 에피소드에 도달했습니다!